Dry-weather flow is the sanitary base load: what the network carries when it is not raining.

1. Customer billing records. The most defensible, because it is measured. Import billing polygons or points with a consumption field; each record is allocated to its nearest manhole and converted to sewer flow.

2. A water network model. If you have an EPANET model of the same area, its demands can drive the sewer directly. Demand becomes sewer flow through the return fraction.

3. Population and per-capita use. The fallback when neither exists. Population comes from building footprints or land-use density, multiplied by per-capita water use.

Whatever the source, sewer flow is:

Q_dwf = R x water demand

R is the return fraction, typically 0.75 to 0.85: the share of supplied water that comes back as wastewater. The rest is irrigation, leakage and consumption.

Peak flow uses a population-dependent peaking factor. This matters more than people expect: peaking is higher for small populations, so a village of 1,700 peaks at roughly 3.6 times average while a town of 10,000 peaks at about 2.9. A single constant factor under-peaks the small systems that need it most.

Sanitary flow is not constant through the day. A diurnal pattern - morning and evening peaks, a night minimum - is applied so the simulated flow varies realistically.

The night minimum is diagnostically useful: in a real network it rarely goes to zero, and what remains is infiltration.